Seitenansicht 1
V5422L / V5422E ACTUATED BUTTERFLY VALVES
EN0B-0319GE51 R0104 2
Table 1. Type list for different valve sizes and corresponding data
actuator current (A)
floating
version
modulating
version
nominal start
run time
(sec)
actuator
torque (Nm)
valve size
(DN)
Kvs
(m
3
/h)
weight
(kg)
V5422L1006 V5422E1001 1.2 1.7 30 600 250 4800 39.2
V5422L1014 V5422E1019 1.2 1.7 30 600 300 7000 48
V5422L1022 V5422E1027 2.0 3.0 30 800 350 8300 60
V5422L1030 V5422E1035 1.2 1.7 60 1200 400 11000 87
V5422L1048 V5422E1043 2.5 3.5 60 1500 450 14000 127
V5422L1055 V5422E1050 2.5 3.5 105 2500 500 18000 193
V5422L1063 V5422E1068 2.5 3.5 120 4000 600 25000 250
GENERAL CHARACTERISTICS
Position Indication and Running Status
The actuator's position is indicated by a mechanical pointer
located behind a window on the actuator's cover.
The actuator's running status is indicated by three LED's
located on the printed circuit board:
The green LED (Op) is lit when the valve has been
opened.
The red LED (Cl) is lit when the valve has been closed.
Angle Limitation
The angle at the drive shaft can be
adjusted to between 0° and 90°.
The end position is limited both
electrically and mechanically. The
electrical limitation can be adjusted by
pressing and turning (with a
screwdriver) the adjustment screws
situated on the white and black cams.
The end position is factory-set to -2°
and +92°. As a rule, it is not necessary
to alter this value.
Emergency Manual Operation
CAUTION
Before manually adjusting the valve, you must first
disconnect the power supply.
It is possible to adjust the valve using the full-disk manual
safety wheel.
Actuators with a valve size of
DN500 and DN600 are
equipped with a manual safety
wheel which is declutched
automatically when the motor
is running. Prior to using the
manual safety wheel, it must
be re-engaged using the
declutch button.
In the case of actuators with a
valve size of DN250 and
DN300, the motor can be
disengaged using the motor
declutch lever.
Motor and Gear Protection
The actuator motor is protected against overheating by a
bimetal temperature monitor.
The motor and gear train are also protected against
mechanical overload by a torque limiter switch. The yellow
LED (Tq) is lit when the torque limiter has been activated.
Maintenance
The actuators are maintenance-free. They are lubricated for
a minimum of 100,000 operations.
If it becomes necessary to renew the grease completely, use
a lubricant complying with the following specifications:
temperature range: -30...+135 °C
penetration: ASTM 265/295 at 25 °C
drop point: 180 °C
E.g. ELF Expecta 250, TOTAL Multis EP2, SHELL alvania
EP2, MOBIL Mobilux EP2, or ESSO Beacon EP2.